Search results for "Transfer phenomenon"

showing 1 items of 1 documents

Safety Concerns on Ground Fault Application Transfer Phenomenon in HV Installations

2007

When a fault to ground occurs in HV/MV substations supplied by a combined overhead-cable line, most of the fault current can be transferred and injected into the soil several kilometers far away from the fault location. This phenomenon is called "fault application transfer" and mostly concerns transition stations, where cables are connected to the overhead line. If the transition station is a dead-end steel pole structure, usually accessible to the general public, the local ground electrode could be inadequate to maintain ground potential rise within safety limits. Hence, dangerous touch and step voltages may appear at exposed locations. In the paper results of various computer simulations …

Settore ING-IND/33 - Sistemi Elettrici Per L'EnergiaEngineeringTransfer phenomenonbusiness.industryGroundTransfer (computing)Electrical engineeringSafety Substations Fault currents Soil Fault location Cables Steel Electrodes Voltage Computer simulationbusinessFault (power engineering)Overhead lineLine (electrical engineering)Voltage2007 IEEE Symposium on Product Compliance Engineering
researchProduct